Design Standards (Applicable to CP TRU / Potentiostat)


These standards govern system design, functional performance, safety, and cathodic protection requirements.


Cathodic Protection & Application Standards


· ISO 15589-1

Petroleum and natural gas industries – Cathodic protection of pipeline transportation systems – On-land pipelines


· EN 12954

Cathodic protection of buried or immersed metallic structures – General principles and application


· AMPP SP0169 (formerly NACE SP0169)

Control of external corrosion on underground or submerged metallic piping systems


· SIST EN 16222:2014 Cathodic Protection of Ship Hulls

(Mentions that the transformer rectifier should have appropriate instrumentation (DC voltmeter, ammeter), control and protection devices, and the ability to deliver the required CP output with controlled ripple.)


Power Electronics & System Safety


· IEC 62477-1

Safety requirements for power electronic converter systems and equipment


· IEC 60146-1-1

Semiconductor converters – General requirements and line-commutated converters


Transformer Component


· IEC 60076-1

Power transformers – General


· IEC 60076-2

Power transformers – Temperature rise


· IEC 60076-5

Power transformers – Ability to withstand short circuit


These clauses are referenced only for transformer design verification, such as insulation class, temperature rise limits, and short-circuit withstand capability. They do not define the overall TRU design or performance.


 Testing Standards (Applicable to Assembled CP TRU)


These standards are used to verify the complete TRU unit, including transformer, rectifier, control system, and enclosure, under operating and environmental conditions.


Environmental & Reliability Tests


· IEC 60068-2-1

Environmental testing – Test A: Cold


· IEC 60068-2-2

Environmental testing – Test B: Dry heat


· IEC 60068-2-78

Environmental testing – Damp heat, steady state


EMC & Electrical Protection


· IEC 61000-4-4

EMC – Electrical fast transient / burst immunity


· IEC 61000-4-5

EMC – Surge immunity test


· IEC 62305

Protection against lightning


Packaging & Transport


· ISO 780

Packaging – Pictorial marking for handling of goods


 Clarification on Applicability


· The CP TRU (Potentiostat) is a dedicated DC power conversion and control system, not a standalone power transformer.


· IEC 60076 is partially applicable and referenced only for the internal transformer component.


· Overall TRU performance is governed by:


o DC output stability (constant current / constant potential)


o Control accuracy


o Ripple factor


o Protection functions


o Environmental reliability


· Therefore, compliance is demonstrated through specific test items, not by applying IEC 60076 as a single governing standard.


This approach is consistent with international CP engineering practice and with equipment previously supplied by EU manufacturers using factory-defined TRU standards.